EMKO TRANS-AMF - Generator Power and Schedule Settings; Generator Power Level Protection

EMKO TRANS-AMF
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9999
9999
9999
9999
9999
9999
kVA
kVA
kVA
kVA
0
0(dis)
0
0
0(dis)
0
Min
Default
Max
Generator Under Power Set
Generator Under Power Pre-Alarm
Generator Under Power Pre-Alarm Reset
Generator Over Power IDMT Alarm
Generator Over Power Set
Generator Over Power Pre-Alarm
0
5
Generator Over Power Pre-Alarm Reset
kVA
kVA
Unit
Generator Over Power Action Delay Time
Reverse Power Set
Reverse Power Action Delay Time
0
-9999
0(dis)
0
99
0
3
99
2
0
0(dis)
2
Sec
kW
Sec
dis
0
0
dis
Reverse Power Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Under power set
Under power prealarm
Under power reset
Over power IDMT alarm
Over power set
Over power prealarm
Over power reset
Over act. delay time
Reverse power set
Reverse power act.
Rv.pow.act.delay time
GEN POWER LEVEL (Generator->Power level)
Generator Under Power Action Delay Time
0(dis)
0
3
99
0(dis)
2
Sec
Generator Under Power Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Under power act.
Under act. delay time
0(dis) 3 0(dis)
Generator Over Power Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Over power act.
Min
Default
Max
Working Calendar Disable or Enable
Working Calendar Work Start Time on Monday
Working Calendar Work Stop Time on Monday
Working Calendar Work Start Time on Tuesday
Working Calendar Work Stop Time on Tuesday
Working Calendar Work Start Time on Wednesday
Working Calendar Work Start Time on Thursday
Working Calendar Work Start Time on Friday
Working Calendar Work Start Time on Saturday
Working Calendar Work Start Time on Sunday
Disable/enable select
Start time on monday
Stop time on monday
Start time on tues.
Stop time on tuesday
Start time on wednes.
Start time on thurs.
Start time on friday
Start time on satur.
Start time on sunday
Unit
Stop time on wednes.
Stop time on thursday
Stop time on friday
Stop time on saturday
Stop time on sunday
Working Calendar Work Stop Time on Wednesday
Working Calendar Work Stop Time on Thursday
Working Calendar Work Stop Time on Friday
Working Calendar Work Stop Time on Saturday
Working Calendar Work Stop Time on Sunday
GEN WORKING CALENDAR (Generator->Working calendar)
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
23.59
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
H.Min
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
23.59
23.59
23.59
23.59
23.59
23.59
23.59
DISBL/ENABL
DISBL
34
ENABL/DISBL DISBL
Over power IDMT alarm
DISABLE: If the measurement value of power more than “Over power set” parameter and this
condition is go on more than “Over act. delay time” parameter, the unit will give a “Over power” alarm.
ENABLE: If the measurement value of power more than “Over power set” parameter and this condition
is go on more than “Tripping time”, the unit will give a “Over power” alarm.
(“Over act. delay time” parameter) x (“Over power set” parameter)
(Measured power) - (“Over power set” parameter)
Tripping time =