Min
Default
START TIMERS (Timers->Start timers)
Max
Mains Transient Delay
Remote Start Delay
Pre-Heat
2.0
Pre-Heat Bypass
0.0 20.0
4
0 3600
3
0 250
0
0 250
Safety On Delay
5
0 99
Horn Duration
60
0 (dis) 999
Charge Excitation Time
15
0 99(cont)
Cooling Fan Time
180
0 250
Remote start delay
Pre-heat
Pre-heat bypass
Safety on delay
Horn duration
Chg. excitation time
Cooling fan time
Mains transient delay
Mains Fail Start Delay
0
0 9999
Mains fail start dely
Mains Transient Delay
Mains Fail Start Delay
Remote Start Delay
Pre-Heat
Pre-Heat Bypass
Safety On Delay
Warmup Time
Horn Duration
Charge Excitation Time
The unit uses this parameter to decide the mains fail.
This timer dictates how long the unit will wait after it has received a mains failure signal before it will
attempt to start. This prevent un-necessary starting on a fluctuating mains supply etc.
This timer dictates how long the unit will wait after it has received a remote start signal before it will
attempt to start. This prevent un-necessary starting on a fluctuating mains supply etc.
This timer dictates the duration that the pre-heat output will be active before an attempt is made to
start the engine. Once this timer is expired cranking will commence.
This feature allows the unit to start a hot engine without performing an un-necessary pre-heat delay.
The bypass timer is triggered by the generator starting and actually being loaded. If the generator
started but does not achieve loading then the timer will not be triggered. The bypass timer is initiated
once the engine has come to rest. If any attempts to start are requested within the duration of the
bypass timer the start sequence will bypass the pre-heat timer.
This timer dictates how long the unit will ignore the Low Oil Pressure, High Engine Temperature,
Underspeed, Undervolts and any other inputs configured as active from safety on. It allows the values
such as oil pressure to rise to their operating values on starting without triggering an alarm. Once the
timer has expired all alarm conditions are monitored again. If configured to use 'fast loading', should all
the monitored conditions, such as oil pressure, come to expected state prior to the end of the safety on
timer, the timer will be terminated prematurely ensuring maximum protection as soon as possible.
This timer is initiated once the engine is up and running. It delays loading the generator until it has
stabilised. Once this timer is expired the 'Close generator' signal will be given and the generator is
available to be loaded.
This timer dictates how long the external horn and the internal sounder will work after the last error
detected. Once after this timer ended unit will do the external horn and the internal sounder reset.
Charge excitation was selectable as momentary / continuous operation.This timer dictates how long
the Charge excitation will active.
Unit
Sec
Min
Sec
Sec
Sec
Sec
Sec
Sec
Sec
Idle Mode Time (Smoke Limiting)
dis
3600
Idle mode time
Idle Mode Time Off (Smoke Limiting Off)
Idle mode time off
Sec
Sec
0 (dis)
0 250 5
Note: dis = disable cont = continuous
73
4.2.7 Timers
Warmup Time
3
0 250
Warming up time
Sec