STOPPING TIMERS (Timers->Stopping timers)
Max
Remote Stop Delay
Cooling Time
4
0 250
60
0 (dis)
3600
Fail To Stop Time
Battery Charging Time
30
5
15
1
99
9999
Remote stop delay
Cooling time
Fail to stop delay
Battery charging time
Mains Return Delay
Remote Stop Delay
Cooling Timer
Fail To Stop Time
Battery Charging Time
This timer dictates how long the unit will wait before it will un-load the generator (back to the mains
supply if AMF) and initialise it's run-on and shutdown cycle. This is ensure that the mains supply has
stabilised before transferring the load back to mains.
This timer dictates how long the unit will wait after it has received a remote stop signal before it will
attempt to stop. This prevent un-necessary stopping on a fluctuating mains supply etc.
This is the time the generator is to run off-load once the load transfer signal has ceased. This gives the
engine time to cool down before shutdown.
Once the unit has given a shutdown signal to the engine it expects the engine to come to rest. It
monitors the Oil pressure and speed sensing sources and if they still indicate engine movement when
this timer expires a 'Fail To Stop' alarm signal is generated.
In AUTO mode and no mains, if one of the configurable inputs are selected as “24-Low Battery” and
this input is active, the unit will perform the start sequence. When the mains back or “Battery Charging
Time” parameter is expired, the unit will perform the stop sequence.
Unit
Sec
Sec
Sec
Min
Cooling Fan Time
Idle Mode Time (Smoke Limiting)
Idle Mode Time Off (Smoke Limiting Off)
This timer dictates how long the Cooling Fan will continue to operate.
This is the amount of time that the smoke limiting output will remain active for once the engine has
started. While the smoke limiting output is active the engine will be held at a reduced speed to
minimise smoke emissions on start-up. (Only if fitted with an appropriate Electronic Control Module).
Once the timer has expired the engine will be allowed to accelerate up to its normal operating speed.
This timer is started after the Idle mode timer (smoke limit timer) was expired. This is to allow the
engine to accelerate to its normal running speed without triggering an underspeed alarm, etc.
74
Note: dis = disable
Mains Return Delay
5
0 3600
Mains return delay
Sec
4.2.8 Expansion Modules
IO (1-8) MODULE (Expansion modules->IO (1-8))
Expansion I/O Module Selection
Disable/enable select
Min
Default
Max
DISBL
ENABL/DISBL
Unit
DIAL-UP & ETHERNET (Expansion modules-> )Dial-up & Ethernet
Expansion Dal-up&Ethernet Module Selection
Call Back Selection
Disable/enable select
Call back selection
Min
Default
Max
ENABL
DISBL
ENABL/DISBL
ENABL/DISBL
Unit
GSM MODULE (Expansion modules->GSM)
Expansion GSM Module Selection
Call Back Selection
SMS Feature Enable or Disable
Disable/enable select
Call back selection
SMS
Min
Default
Max
ENABL
DISBL
DISBL
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
Unit