Note: dis = disable
Operator Password
Technician Password
Use this option to change the Operator password. This password allows access to operator
parameters section.
Use this option to change the Technician password. It allows access to both operator and technician
parameters section.
Min
DefaultDATE & TIME SET (System->Date & time set)
Max
Year
Month
0 99
1
12
Date
1
31
Day of week
1
7
Hour
0
23
Minute
0
59
Second
0
59
Year
Month
Day
Week
Hour
Minute
Second
Unit
Min
Default
Unit
PASSWORD SETTINGS (System->Password settings)
Max
Operator Password
Technician Password
0
0 9999
0
9999 0
Operator password
Technician password
Min
Default
Unit
DEFAULT SETTINGS (System->Default settings)
Max
Save setting to default
Reset default sets
Save setting to def.
Reset default sets
YES / NO NO
Reset factory sets
Reset factory sets
YES / NO NO
YES / NO NO
Save setting to default
If this parameter is selected as “Yes”, the unit’s currently parameters save as default sets.
After this parameter is reset automatically to “No”.
Reset default sets
If this parameter is selected as “Yes”, the unit’s parameters back to default sets.
After this parameter is reset automatically to “No”.
Reset factory sets
If this parameter is selected as “Yes”, the unit’s parameters back to factory sets.
After this parameter is reset automatically to “No”.
Day of week 1=Monday,2=Tuesday,3=Wednesday,4=Thursday,5=Friday,6=Saturday,7=Sunday
Min
Default
Unit
COMMUNICATION (System->Communication)
Max
Slave Address
1
1 247
0
5 3
Baud Rate: 0 - 1200 baud
1 - 2400 baud
2 - 4800 baud
3 - 9600 baud
4 - 19200 baud
5 - 38400 baud
Datalog Period
Timeout
Stop Bit (0-> 1 stop bit,1-> 2 stop bit)
0
2
0
0.0(dis)
0(dis)
0
999.9
999
1
1.0
dis
0
Slave address
Baud rate
Parity
Datalog period
Timeout
Stop bit
Parity: 0 - NONE
1 - ODD
2 - EVEN
Min
Min
Timeout
This parameter is used for the modem hardware reset.
If the data communication is interrupted and this situation continues as this parameter, the modem
hardware reset is performed.