Oil Pressure Input Type
This section is used to configure the Oil Pressure sender input.
0 NOT USED: The Oil Pressure input will not be monitored.
1 DIGITAL NC: The Oil pressure input is fed from an engine mounted digital pressure switch. This
switch returns a closed signal during low oil pressure conditions (and engine at rest), once oil pressure
is established the switch will open.
2 DIGITAL NO: The Oil pressure input is fed from an engine mounted digital pressure switch. This
switch returns an open signal during low oil pressure conditions (and engine at rest), once oil pressure
is established the switch will close.
3, 4, 5, 6, 7, 8 and 9: Oil pressure input is connected to a resistive type engine mounted oil pressure
transducer. If this parameter selected as "9 USER CONFIGURED", the user can input the data
manually according to the sensor curve.
Temperature Input Type
This section is used to configure the Coolant Temperature sender input.
0 NOT USED: The Coolant Temperature input will not be monitored.
1 DIGITAL NC: The Coolant Temperature input is fed from an engine mounted digital temperature
switch. This switch returns a closed signal during low temperature, should the temperature rise above
the switch manifacturers trip point the switch contact will open.
2 DIGITAL NO: The Coolant Temperature input is fed from an engine mounted digital temperature
switch. This switch returns an open signal during low temperature, should the temperature rise above
the switch manifacturers trip point the switch contact will close.
3, 4, 5, 6, 7 and 8: The Coolant Temperature input is connected to a resistive type engine mounted
temperature transducer. If this parameter selected as "8 USER CONFIGURED", the user can input the
data manually according to the sensor curve.
Temperature Sensor Break
: The Coolant Temperature sensor break will not be monitored.
ENABLE: The Coolant Temperature sensor break will be monitored if the engine runs at least 3
minutes.
This section is used to configure the sender input.
0 NOT USED: The will not be monitored.
1 DIGITAL NC: open for low .
2 DIGITAL NO: close for low .
3, 4, 5, 6, 7 and 8: The input is connected to a resistive type engine
mounted level/temperature/pressure transducer. If this parameter selected as "8 USER
CONFIGURED", the user can input the data manually according to the sensor curve.
This section is used to configure the sender input.
0 NOT USED: The will not be monitored.
1 DIGITAL NC: open for low .
2 DIGITAL NO: close for low .
3, 4, 5, 6, 7 and 8: The input is connected to a resistive type engine
mounted level/temperature/pressure transducer. If this parameter selected as "8 USER
CONFIGURED", the user can input the data manually according to the sensor curve.
-
-
-
-
-
-
-
-
DISABLE
Configurable Analog Input-1 Type
Configurable Analog Input-1
- Configurable Analog Input-1
- Configurable Analog Input-1
- Configurable Analog Input-1
Configurable Analog Input-1
-
Configurable Analog Input-2 Type
Configurable Analog Input-2
- Configurable Analog Input-2
- Configurable Analog Input-2
- Configurable Analog Input-2
Configurable Analog Input-2
-
50

Table of Contents

Other manuals for EMKO TRANS-AMF

Related product manuals