75
4.2.9 User Adjustment
Min
Default
Unit
MAINS VOLTAGE OFFSET (User adjustment->Mains voltage offset)
Max
0
0
0
-20
-20
-20
Mains V1 offset
Mains V2 offset
Mains V3 offset
Mains V1 Offset
Mains V2 Offset
Mains V3 Offset
20
20
20
VV
VV
VV
Min
Default
Unit
GEN. VOLTAGE OFFSET (User adjustment->Gen. voltage offset)
Max
0
0
0
-20
-20
-20
Gen. V1 offset
Gen. V2 offset
Gen. V3 offset
Generator V1 Offset
Generator V2 Offset
Generator V3 Offset
20
20
20
VV
VV
VV
Min
Default
Unit
CURRENT OFFSET (User adjustment->Current offset)
Max
0
0
0
0
-20
-20
-20
-20
Current I1 offset
Current I2 offset
Current I3 offset
E/F. Current offset
Current I1 Offset
Current I2 Offset
Current I3 Offset
Earth current I3 Offset
20
20
20
20
AV
AV
AV
AV
Min
Default
Unit
BATTERY&CHRG GEN.VOL (User adjustment->Battery&chrg gen.vol)
Max
0
0
-5.0
-5.0
Batt.volt offset
Gen.chg.volt offset
Battery Voltage Offset
Charge Generator Voltage Offset
5.0
5.0
VZ
VZ
Min
Default
Unit
SENDER INPUTS OFFSET (User adjustment->Sender inputs offset)
Max
0.0
0
0
0
-2.0
-20
-200
-20
Oil Pressure offset
Temperature offset
Conf. AI1 offset
Conf. AI2 offset
Oil Pressure Offset
Coolant Temperature Offset
Configurable Analog Input-1 Offset
Configurable Analog Input-2 Offset
2.0
20
200
20
BAR
ºC
ºC
%
GPRS MODULE (Expansion modules->GPRS)
Expansion GPRS Module Selection
Call Back Selection
GPS Feature Enable or Disable
Disable/enable select
Call back selection
GPS
Min
Default
Max
1-SERVER
DISBL
DISBL
0-DISABLE
1-SERVER
2-CLIENT
ENABL/DISBL
ENABL/DISBL
Unit
DUAL SET MODULE (Expansion modules->Dual set)
Expansion Dual Set Module Selection
Node Address
Dual Working Period
Early Start Time
Remote Priority Selection:
Disable/enable select
1
*
Node ID
2
*
Working period
Early start time
Remote priority selct
Min
Default
Max
1
0:00
0
0(dis)
2
9:59
250
2
1
1:00
15
dis
H.Min
Sec
0- Disable, 1- Priority, 2- None Priority
Unit
ENABL
ENABL/DISBL
WEB SERVER MODULE (Expansion modules->Web Server)
Web Server Module Selection
Disable/enable select
Min
Default
Max
ENABL
ENABL/DISBL
Unit
GPRS WEB MODULE (Expansion modules->GPRS Web)
GPRS-Web Module Selection
Disable/enable select
Min
Default
Max
ENABL
ENABL/DISBL
Unit
1
Note: * =
2
* =
dis = disable.
Changing this parameter becomes only effective after restarting the unit.
Changing this parameter becomes only effective after restarting the unit.