5. Specifications
79
Equipment use : Electrical control equipment for generating sets.
Housing & Mounting : 229 mm x 152 mm x 41 mm. (including connectors). Plastic
housing for panel mounting.
Panel Cut-Out : 182mm x 135mm.
Protection : IP65 at front panel.
Weight : Approximately 0,53 Kg.
Environmental rating : Standard, indoor at an altitude of less then 2000 meters
with non-condensing humidity.
Operating/Storage Temperature : -20°C to +70°C / -30°C to +80°C
Operating/Storage Humidity : 90 % max. (non-condensing)
Installation Over Volt. Category : II Appliances, portable equipment
Pollution Degree : II, Normal office or workplace, non conductive pollution
Mode of Operation : Continuous.
DC Battery Supply Voltage : 8 to 32 V Z. Max. operating current is 360 mA.
Cranking Dropouts : Battery voltage can be “0” VDC for max. 50 ms during
cranking (battery voltage should be at least nominal
voltage before cranking).
Battery Voltage Measurement : 8 to 32 V Z, accuracy: 1 % FS, resolution: 0,1 V
Mains Voltage Measurement : 3 to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
Resolution: 1 V.
Mains Frequency : 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
Generator Voltage Measurement : 3 to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
Resolution: 1 V.
Generator Frequency : 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
Magnetic Pickup Input : 35 to 10000 Hz (1 to 35 volts peak continuously).
Accuracy: 0,25 % FS.
CT secondary : 5A.
Charge Generator Excitation : 210mA @12V, 105mA @24V. Nominal 2.5W.
Charge Gen. Vol. Measurement : 8 to 32 V Z, accuracy: 1 % FS, resolution: 0,1 V.
Sender Measurement : 0 to 1300 ohm, accuracy: 1 % FS, resolution: 1 ohm.
Canbin Temp. Measurement : -50 to +100 ºC, accuracy: 1 % FS, resolution: 1 ºC.
Communication interface : USB programming and communication port,
CanBus communication with 1939 ECU
Optional Expansion I/O Module : Expansion I/O module including 8 inputs and 8 outputs.
Optional Comm. Modules : Ethernet/Dial-up, GSM/GPRS, RS-485, Dual Set,
Web Server and GPRS-Web modules.
Relay Outputs : Generator contactor relay output 8A@250VV
Mains contactor relay output 8A@250VV
Configurable output-5 5A@250VV
Configurable output-6 5A@250VV
Transistor Outputs : Fuel or Configurable output-1 1A at DC supply voltage
Crank or Configurable output-2 1A at DC supply voltage
Configurable output-3 1A at DC supply voltage
Configurable output-4 1A at DC supply voltage
All transistor ouputs supplied from DC supply terminal 22