1.Introduction
1.1 General Specifications
4
The unit provides for automatic transfer of a load from mains to generator in the event of a
mains failure. Intended for unattended operation, it is able to detect failure of any phase of the
mains and to start and switch over to a generator if the mains voltage goes outside pre-set
limits. Both automatic and manual control is possible. A test mode is also available which
allows the generator to be run without taking the load.
The unit has Dual Working feature. In the event of a mains failure, group with high priority
starts and takes the load. If both groups has no priority, the group with less working hour will
start and take the load. To use Dual Working feature Dual Set expansion module must be
used.
The unit calculates engine RPM from Magnetic Pickup sensor input (MPU) and/or generator
voltage signal.
The unit monitors J1939 ECU messages and provides remote start/stop control via J1939
protocol (supported ECUs: Volvo EMS2, Volvo EDC4, Perkins, Scania S6, MAN MFR and
standard messages).
The unit is extensively programmable through the front panel, with password protection on two
levels. Operational parameters can also be monitored and controlled from a PC via a built-in USB
communication port.
.
The unit monitors generator operation and gives warning of any faults that are detected.
The configurable input-3 can be used as the water level sensing input.
The configurable input-7 can be used as the cabin temperature analog input.
In the event that the engine fails to start on the first attempt, the attempt will be repeated a
programmed number of times or until successful
If a fault is detected, the unit shuts down the engine and shows the failure message on the LCD
display and activates the internal sounder.
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.