114 LOAD SUPPLY FROM MAINS
This output indicates that the load is supplying from mains.
115 CONFIGURABLE ANALOG INPUT-1 LOW PRE-ALARM
This output indicates that a low configurable analog input-1 warning (pre-alarm) has occurred.
116 CONFIGURABLE ANALOG INPUT-1 LOW SHUTDOWN
This output indicates that a low analog input-1 shutdown has occurred.
117 CONFIGURABLE ANALOG INPUT-2 LOW PRE-ALARM
This output indicates that a low configurable analog input-1 warning (pre-alarm) has occurred.
118 CONFIGURABLE ANALOG INPUT-2 LOW SHUTDOWN
This output indicates that a low analog input-2 shutdown has occurred.
119 CONFIGURABLE ANALOG INPUT-2 HIGH PRE-ALARM
This output indicates that a high analog input-2 warning (pre-alarm) has occurred.
120 CONFIGURABLE ANALOG INPUT-2 HIGH SHUTDOWN
This output indicates that a high analog input-2 shutdown has occurred.
121 CHOKE ACTIVE
This ouput becomes active everytime generator cranks and stays active until the choke time expires.
122 REMOTE CONTROL ACTIVE
This output indicates that the engine is being controlled remotely.
123 REVERSE POWER
This ouput becomes active when generator’s active power drops below the Reverse Power Set value.
124 CABIN TEMPERATURE LOW PRE-ALARM
This output indicates that a low cabin temperature warning (pre-alarm) has occurred.
125 CABIN TEMPERATURE LOW SHUTDOWN
This output indicates that a low cabin temperature shutdown has occurred.
126 CABIN TEMPERATURE HIGH PRE-ALARM
This output indicates that a high cabin temperature warning (pre-alarm) has occurred.
127 CABIN TEMPERATURE HIGH SHUTDOWN
This output indicates that a high cabin temperature shutdown has occurred.
128 HEATER CONTROL
Becomes active when the Coolant Temperature falls below the "Heater control ON" setting. If the output is
already active it will become inactive when the Coolant Temperature is above the “Heater control OFF" setting.
129 REMOTE OUTPUT
This output indicates that the output can be energised or de-energised remotely.
130 UNBALANCE LOAD
This output indicates “out of balance” current loading of the generator.
Sometimes also called Negative Sequence Current or Symmetry Fault.
131 WATER PUMP
This output becomes active for the “Water pump on time” parameter and passive for the “Water pump off time”
parameter while the "Heater control output" was active.
72