94 REMOTE START PRESENT
This output indicates that a digital input that has been configured as 'remote start' is active. This output could be
used to pass the remote start signal on to else where in the control system.
95 REMOTE STOP DELAY IN PROGRESS
This output source will be active to indicate that the return timer is running.
96 SHORT CIRCUIT
This output indicates that the module has detected a short circuit on the generator output.
97 SMOKE LIMITING
This output is used to supply a smoke-limiting signal to an Electronic Governor to limit smoke emissions on start-
up. It is used in conjunction with the Smoke limit timer (Idle mode timer) settings. Once the timer has expired, the
Smoke limit output will cease to operate allowing the engine to accelerate to normal running speed.
98 STARTING ALARM
This output is used to supply an external sounder with a signal that the engine is about to start. The output will be
active during the start delay and pre-heat timer (if used).
99 STARTING ALARMS ARMED
The output indicates that the starting alarms are now enabled. It can be used to control external logic circuitry.
Starting alarms are armed as soon as the unit commences starting of the engine and remain armed until the
engine at rest.
100 STOP RELAY ENERGISED
The output mimics the operation of the stop relay. Can be used to control external logic circuitry.
101 SYSTEM IN AUTO MODE
The output indicates that the unit is in the Auto mode.
102 SYSTEM IN MANUAL MODE
The output indicates that the unit is in the Manual mode.
103 SYSTEM IN STOP MODE
The output indicates that the unit is in the Stop mode.
104 SYSTEM IN TEST MODE
The output indicates that the unit is in the Test mode.
105 UNDER CURRENT PRE-ALARM
This output indicates that the under current pre-alarm has been reached.
106 UNDER CURRENT ALARM
This output indicates that the under current trip level has been reached.
107 UNDER POWER PRE-ALARM
This output indicates that the under power pre-alarm has been reached.
108 UNDER POWER SHUTDOWN
This output indicates that the under power shutdown has been reached.
109 UNDER SPEED PRE-ALARM
This output indicates that an under speed warning (pre-alarm) has occurred.
110 UNDER SPEED SHUTDOWN
This output indicates that an under speed shutdown has occurred.
111 WAITING FOR GENERATOR
This output indicates that the engine has been instructed to start but has not yet become available. Once the
generator becomes available this output will be in-active.
112 DUAL COMMUNICATION ERROR
This output indicates that an dual communication alarm has occurred.
113 LOAD SUPPLY FROM GENERATOR
This output indicates that the load is supplying from generator.
71