70
75 MAINS LOW FREQUENCY
This output indicates that the unit has sensed that the incoming AC mains supply frequency has fallen below the
frequency setting.
76 MAINS LOW VOLTAGE
This output indicates that the unit has sensed that the incoming AC mains supply voltage has fallen below the
voltage limit setting.
77 MAINS OPEN BREAKER
This output used to control the load switching device. For Details see: "BREAKERS Page" section.
78 NO LOADING COMMAND
This output indicates that the unit is not calling of the generator contactor or breaker to be closed. Should the unit
close the generator contactor this output will become inactive.
79 OIL PRESSURE LOW PRE-ALARM
This output indicates that a low oil pressure warning (pre-alarm) has occurred.
80 OIL PRESSURE LOW SHUTDOWN
This output indicates that a low oil pressure shutdown has occurred.
81 CONFIGURABLE ANALOG INPUT-1 HIGH PRE-ALARM
This output indicates that a high analog input-1 warning (pre-alarm) has occurred.
82 CONFIGURABLE ANALOG INPUT-1 HIGH SHUTDOWN
This output indicates that a high analog input-1 shutdown has occurred.
83 OVER CURRENT PRE-ALARM
This output indicates that the over current pre-alarm has been reached.
84 OVER CURRENT ALARM
This output indicates that the over current trip level has been reached.
85 OVER POWER PRE-ALARM
This output indicates that the over power pre-alarm has been reached.
86 OVER POWER SHUTDOWN
This output indicates that the over power shutdown has been reached.
87 OVER SPEED PRE-ALARM
This output indicates that the over speed warning (pre-alarm) has occurred.
88 OVER SPEED SHUTDOWN
This output indicates that the over speed shutdown has occurred.
89 PANEL LOCK
This output indicates that the unit ‘panel lock’ is active. If the panel lock input is active, the unit will not respond to
operation of the Mode select or start buttons. This allows the unit to be placed into a specific mode (such as
auto) and then secured.
90 PRE-HEAT(during preheat timer)
The output controls the pre-heater. Pre-heat output is available for the duration of pre-heat timer, which
terminates prior to cranking.
91 PRE-HEAT(until end of cranking)
The output controls the pre-heater. As 'Pre-heat (during pre-heat timer)' mode but pre-heat is also available
during cranking.
92 PRE-HEAT(until end of warming)
The output controls the pre-heater. As 'Pre-heat (until safety on)' but pre-heat continues to be available until the
warm-up timer has elapsed.
93 PRE-HEAT(until end safety on)
The output controls the pre-heater. As 'Pre-heat (until end of cranking)' but pre-heat is also available while
waiting for the delayed alarms to become active.