57 GENERATOR LOW VOLTAGE PRE-ALARM
This output indicates that a generator low voltage warning (pre-alarm) has occurred.
58 GENERATOR LOW VOLTAGE SHUTDOWN
This output indicates that a generator low voltage shutdown has occurred.
59 GENERATOR STOPPING
This output indicates that the engine has been instructed to stop but has not come to rest.
60 GENERATOR OPEN BREAKER
This output used to control the load switching device. For Details see: "BREAKERS Page" section.
61 HORN OUTPUT LATCHED
This output indicates that the latched horn alarm has occurred.
62 HORN OUTPUT PULSED
This output indicates that the pulsed horn alarm has occurred.
63 LAMP TEST
This output indicates that the module is performing a lamp test. Once the lamp test completed, the output will
become inactive again. The output can be used to feed a lamp test on external modules or panel lamps.
64 CONFIGURABLE ANALOG INPUT-2 CONTROL
Becomes active when the Analog Input-2 falls below the "ANALOG INPUT-2 ON" setting. If the output is already
active it will become inactive when the Analog Input-2 is above the “ANALOG INPUT-2 OFF" setting.
65 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
This output indicates that the magnetic pick up signal is not sufficient to be used by the unit for speed monitoring.
The alarm can only operate if the speed signal fails to appearduring cranking. It is disabled if ‘multiple attempts to
engage’ is selected. If the MPU fails during engine running this would result in an under speed alarm.
66 LOW TEMPERATURE
This output indicates that a low temperature warning has occurred.
67 MAINTENANCE DUE ALARM
This output indicates that the generator is now due for maintenance either because it has used all the available
running hours or the periodic maintenance time has expired. To clear the output a maintenance reset must be
performed.
68 MAINS CLOSED AUXILIARY
This output indicates that a digital input that has been configured as 'mains closed auxiliary' is active.
69 MAINS FAILED TO CLOSE
This output source has intended to be used to indicate a failure of the mains contactor or breaker. It can only be
used if the unit is configured to use 'mains closed auxiliary' feedback.
70 MAINS FAILED TO OPEN
This output source has intended to be used to indicate a failure of the mains contactor or breaker. It can only be
used if the unit is configured to use 'mains closed auxiliary' feedback.
71 MAINS FAILURE
This output indicates that the unit has sensed that a failure of the incoming AC mains supply. This output will
become active whenever the mains voltage or frequency goes out of limits, or if the auxiliary mains failure input
active (if used) and the mains transient timer has expired.
72 MAINS HIGH FREQUENCY
This output indicates that the unit has sensed that the incoming AC mains supply frequency has exceeded the
frequency limit setting.
73 MAINS HIGH VOLTAGE
This output indicates that the unit has sensed that the incoming AC mains supply voltage has exceeded the
voltage limit setting.
74 MAINS LOAD INHIBIT
This output indicates that a digital input has been configured as 'mains load inhibit' is active.