37 EXPANSION CONFIGURABLE INPUT8 ALARM
This output indicates that expansion configurable input 8 alarm has occurred.
38 EARTH FAULT
This output indicates that the unit has detected that an earth fault exists on the generator output.
39 EMERGENCY STOP
This output indicates that an emergency stop alarm has occurred.
40 FAIL TO START ALARM
This output indicates that the engine has not started after the specified number of attempts.
41 FAIL TO STOP ALARM
This output indicates that the generator has failed to stop within the selected time
42 CONFIGURABLE ANALOG INPUT-1 CONTROL
Becomes active when the Analog Input-1 falls below the "ANALOG INPUT-1 ON" setting. If the output is already
active it will become inactive when the Analog Input-1 is above the “ANALOG INPUT-1 OFF" setting.
43 FUEL RELAY ENERGISED
The output mimics the operation of the fuel relay. It can be used to control external logic circuitry.
44 GAS ENGINE IGNITION OUTPUT
With the engaging of the starter the ignition delay is started. If the ‘minimum ignition speed’ is reached after
expiry of this time, the configurable relay output ‘ignition’ is set. When the necessary engine shutdown process,
firstly gas valve is de-energised. Then ignition output is de-energised that after 5 seconds when the engine
speed become lower than ‘minimum ignition speed’
45 GENERATOR AT REST
The output indicates that the generator is not running.
46 GENERATOR AVAILABLE
This output indicates when the generator is ready to accept load, i.e. after safety on and warm up timers have
timed out.
47 GENERATOR CLOSED AUXILIARY
This output indicates that a digital input that has been configured as 'generator closed auxiliary' is active.
48 GENERATOR FAILED TO CLOSE
This output source has intended to be used to indicate a failure of the generator contactor or breaker. It can only
be used if the unit is configured to use 'generator closed auxiliary' feedback.
49 GENERATOR FAILED TO OPEN
This output source has intended to be used to indicate a failure of the generator contactor or breaker. It can only
be used if the unit is configured to use 'generator closed auxiliary' feedback.
50 GENERATOR HIGH FREQUENCY PRE-ALARM
This output indicates that a generator high frequency warning (pre-alarm) has occurred.
51 GENERATOR HIGH FREQUENCY SHUTDOWN
This output indicates that a generator high frequency shutdown has occurred.
52 GENERATOR HIGH VOLTAGE PRE-ALARM
This output indicates that a generator high voltage warning (pre-alarm) has occurred.
53 GENERATOR HIGH VOLTAGE SHUTDOWN
This output indicates that a generator high voltage shutdown has occurred.
54 GENERATOR LOAD INHIBIT
This output indicates that a digital input has been configured as 'generator load inhibit' is active.
55 GENERATOR LOW FREQUENCY PRE-ALARM
This output indicates that a generator low frequency warning (pre-alarm) has occurred.
56 GENERATOR LOW FREQUENCY SHUTDOWN
This output indicates that a generator low frequency shutdown has occurred.