67
15 COMMON WARNING ALARM
This output indicates that a warning alarm has been activated. This output is normally self-resetting on removal
of the fault.
16 COOLING FAN AFTER START
This output should energise as soon as engine has started so the fan should be running when the engine is
running. This output should continue to operate for Cooling Fan Time parameter after engine has stopped.
17 COOLING FAN AFTER STOP
This output indicates that can be made to energise for Cooling Fan Time parameter after the engine shuts down
(to run an electric cooling fan on the radiator).
18 COOLANT TEMPERATURE HIGH PRE-ALARM
This output indicates that a high engine coolant temperature warning (pre-alarm) has occurred.
19 COOLANT TEMPERATURE HIGH SHUTDOWN
This output indicates that a high engine coolant temperature shutdown has occurred.
20 COOLING DOWN TIMER IN PROGRESS
This output source will be active when the cooling off-load timer is running.
21 CRANK RELAY ENERGISED
The output mimics the operation of the crank relay. Can be used to control external logic circuitry.
22 DELAYED ALARMS ACTIVE
The output indicates that the delayed alarms now enabled. Can be used to control external logic circuitry.
23 DIGITAL INPUT1 ALARM
This output indicates that digital input 1 alarm has occurred.
24 DIGITAL INPUT2 ALARM
This output indicates that digital input 2 alarm has occurred.
25 DIGITAL INPUT3 ALARM
This output indicates that digital input 3 alarm has occurred.
26 DIGITAL INPUT4 ALARM
This output indicates that digital input 4 alarm has occurred.
27 DIGITAL INPUT5 ALARM
This output indicates that digital input 5 alarm has occurred.
28 DIGITAL INPUT6 ALARM
This output indicates that digital input 6 alarm has occurred.
29 DIGITAL INPUT7 ALARM
This output indicates that digital input 7 alarm has occurred.
30 EXPANSION CONFIGURABLE INPUT1 ALARM
This output indicates that expansion configurable input 1 alarm has occurred.
31 EXPANSION CONFIGURABLE INPUT2 ALARM
This output indicates that expansion configurable input 2 alarm has occurred.
32 EXPANSION CONFIGURABLE INPUT3 ALARM
This output indicates that expansion configurable input 3 alarm has occurred.
33 EXPANSION CONFIGURABLE INPUT4 ALARM
This output indicates that expansion configurable input 4 alarm has occurred.
34 EXPANSION CONFIGURABLE INPUT5 ALARM
This output indicates that expansion configurable input 5 alarm has occurred.
35 EXPANSION CONFIGURABLE INPUT6 ALARM
This output indicates that expansion configurable input 6 alarm has occurred.
36 EXPANSION CONFIGURABLE INPUT7 ALARM
This output indicates that expansion configurable input 7 alarm has occurred.