33
Min
Default
Max
Generator Under Current Pre-Alarm Reset
Generator Under Current Actions Delay Time
Generator Over Current IDMT Alarm
Generator Over Current Set
Generator Over Current Pre-Alarm
Generator Over Current Pre-Alarm Reset
Generator Over Current Actions Delay Time
Generator Short Circuit Current Set
Generator Earth Fault Current Set
Generator Earth Fault Current Actions Delay Time
Under cur. reset
Under cur. act.
Under act. delay time
Over cur. IDMT alarm
Over cur. set
Over cur. prealarm
Over cur. reset
Over cur. act.
Over act. delay time
Short circuit cur.
Earth fault cur.
Earth fault cur. act.
E.F. act. delay time
Unit
GEN CUR LEVEL & ACT (Generator->Current level & act.)
Generator Under Current Set
Under cur. set
Under cur. prealarm
Generator Under Current Pre-Alarm
0
0(dis)
0
0
0
0(dis)
0
9999
3
99
9999
9999
3
99
9980
dis
2
9999
100
dis
2
AV
AV
AV
0
0(dis)
0
0(dis)
0
0
0(dis)
9999
9999
9999
3
99
9999
9999
1
dis
5
dis
2
9999
9990
AV
AV
AV
AV
AV
Sec
Sec
Sec
Generator Under Current Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Generator Over Current Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Generator Earth Fault Current Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Unbalance Load Set
Unbalance Load Actions Delay Time
Unbalance load set
Unbalance load act.
Unbalance act. delay
0
0(dis)
0
9999
3
99
0
dis
2
AV
Sec
Unbalance Load Actions
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
ENABL/DISBL DISBL
Over cur. IDMT alarm
DISABLE: If the measurement value of current more than “Over cur. set” parameter and this condition
is go on more than “Over act. delay time” parameter, the unit will give a “Over current” alarm.
ENABLE: If the measurement value of current more than “Over cur. set” parameter and this condition
is go on more than “Tripping time”, the unit will give a “Over current” alarm.
(“Over act. delay time” parameter) x (“Over cur. set” parameter)
(Measured current) - (“Over cur. set” parameter)
Tripping time =