©2020 EMS Ltd. All rights reserved Page 21 of 36 MK349-0001-99 (Issue 1) 22/10/2020 AJM
Menu Selection Available options
Text Description
Detection
Smoke Sen
Heat Sen
Sound Volume
Self Sound
Audio/Visual
O/P 1 OFF
O/P 2 OFF
Refer to the ‘Device location text’ section overleaf.
Detection selection of ‘Dual’ (smoke & heat),
‘Smoke Only’ or ‘Heat Only’.
Smoke sensitivity selection of; ‘Normal*†’ and
‘Normal + AVF’. The AVF option allows additional
verification of the alarm condition before
reporting.
Heat sensitivity selection of; ‘58 °C static*†’, ‘58 °C
rate of rise*’, ‘72 °C static*’, ‘72 °C rate of rise*’.
Allows device sounder levels of; ‘High’ or ‘Low’.
When enabled, the device will sound upon local
alarm detection, whilst wireless communication
with the WZM is lost.
Allows device sounder and beacon selection of;
sounder & beacon, sounder only and beacon only.
Choose to switch the devices ‘Output 1’ off, when
either the ‘silence’ or ‘reset’ button is pressed.
Choose to switch the devices ‘Output 2’ off, when
either the ‘silence’ or ‘reset’ button is pressed.
*Approved EN54 sensitivities † Default dual sensitivities