TONE TONE TYPE TONE DESCRIPTION / APPLICATION
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
970Hz
800Hz/970Hz at 2Hz
800Hz - 970Hz at 1Hz
970Hz 1s OFF / 1s ON
970Hz, 0.5s / 630Hz at 1 Hz
554Hz, 0.1s / 440Hz, 0.4s (AFNOR NF S 32 001)
500 - 1200Hz, 3.5s / 0.5s OFF (NEN 2575:2000 Dutch slow whoop)
420Hz 0.6s ON / 0.6s OFF (Australia AS1670 Alert tone)
1000 - 2500Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 Evacuation)
550Hz / 440Hz at 0.5Hz
970Hz, 0.5s ON / 0.5s OFF x 3 / 1.5s OFF (ISO 8201)
2850Hz, 0.5s ON / 0.5s OFF x 3 / 1.5s OFF (ISO 8201)
1200Hz - 500Hz at 1Hz (DIN 33 404)
400Hz
550Hz, 0.7s / 1000Hz, 0.33s
1500Hz - 2700Hz at 3Hz
750Hz
2400Hz
660Hz
660Hz 1.8s ON / 1.8s OFF
660Hz 0.15s ON / 0.15s OFF
510Hz, 0.2s / 610Hz, 0.2s
800 / 1000Hz 0.5s each (1Hz)
250Hz - 1200Hz at 12Hz
500Hz - 1200Hz at 0.33Hz
2400Hz - 2900Hz at 9Hz
2400Hz - 2900Hz at 3Hz
500 - 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation)
800Hz - 970Hz at 9Hz
800Hz - 970Hz at 3Hz
800Hz, 0.25s ON / 1s OFF
500Hz - 1200Hz, 3.75s / 0.25s OFF (AS2220)
3
3
Note: Tones 1, 4, 5 and 7 are EN54-3 approved tones.
**Default fire tone**