Configuration
parameters (cont.)
Parameter Description
Select Pressure
Unit
Changes the pressure units. Options: mbar, bar, Pa, hPa, kPa, MPa, mm
H
2
O, m H
2
O, in H
2
O, ft H
2
O, psi, g/cm
2
, kg/cm
2
, kgf/cm
2
, atm, Ib/ft
2
, Torr,
mm Hg or in Hg (All pressure-specific parameters are recalculated and
shown in these units.)
Diagnostic Code *
Indicates the current diagnostic code with associated message of any
device alarm, see Chapter 7.1.
Last
Diagnostic *
Indicates the previous diagnostic code with message registered by the
device, see Chapter 7.1.
Clear Last
Diagnostic Code
Clears last diagnostic code. Options: # – no action, clear – message is
delected
Transducer_sw_
vers *
Indicates the measuring software version of the device.
Min. Pressure *
Maximum pointer function for the smallest measured pressure value
Reset Min. Pres
Peak Hold
Options: # – no action, reset – Acting pressure value is adopted for the
parameter "Min. Pressure".
Max. Pressure *
Maximum pointer function for the largest measured pressure value
Reset Max. Pres
Peak Hold
Options: # – no action, reset – Acting pressure value is adopted for the
parameter "Max. Pressure".
Integer
Counter high *
Counter for pressure values above the upper range-limit (parameter "High
Sensor Calibration"), max value = 255
Options: # – no action, clear – counter is reset to "0"
Sensor
Temperature *
Display of actual measured temperature in the selected unit
Min. Temperature
*
Maximum pointer function for the smallest measured temperature
Reset min
Temp. Peak Hold
Options: # – no action, reset – Current temperature is adopted for the
parameter "Min. Temperature".
Max.Temperature
*
Maximum pointer function for the largest measured temperature
Reset max
Temp. Peak Hold
Options: # – no action, reset – Current temperature is adopted for the
parameter "Max. Temperature".
DefaultValues
When "5140" is entered here the device parameters are reset to their
factory setting, see Chapter 7.2.
Linearization
(operating mode)
Adjusting the operating mode. Options: linear (pressure), square root
function (flow), level linear (level, volume or weight), level horizontal
cylinder (volume and weight)
Start Point
For operating modes: "square root function", "level linear" and "level
horizontal cylinder" – zero for output scaling (corresponds to lower
range-value)
Full Scale
For operating modes: "square root function", "level linear" and "level
horizontal cylinder" – scale value for output scaling (corresponds to upper
range-value)
Unit After
Liniarization
Selecting units for measuring the level, volume, weight or flow – the
options depend on the operating mode selected. The linearized value is
shown in "Measured Value" in these units. The measured value is not
converted into the new units.
* Display value
3 Foundation Fieldbus Interface Cerabar S FF
22 Endress+Hauser