Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
100 Endress+Hauser
High High Priority/
HI_HI_PRI
Entry
Index: 25
Data type: unsigned8
Access: auto, man, OOS
Specify how the system should react if the High High Limit/HI_HI_LIM limit value
(→ ä 100) is overshot.
Input range:
•0 to 15
• 0: The alarm is suppressed.
• 1: The alarm is detected by the system. No notification is issued.
• 2: Reserved for block alarms.
• 3-7: Informative alarm with increasing priority,
3: Low priority, 7: High priority
• 8-15: Critical alarm with increasing priority,
8: Low priority, 15: High priority
Factory setting:
0
High High Limit/
HI_HI_LIM
Entry
Index: 26
Data type: float
Access: auto, man, OOS
Enter upper critical limit value.
Input range:
Range and units of Output Scale/OUT_SCALE (→ ä 96)
Factory setting:
+INF
High Priority/HI_PRI
Entry
Index: 27
Data type: unsigned8
Access: auto, man, OOS
Specify how the system should react if the High Limit/HI_LIM limit value (→ Page 100) is
overshot.
Input range:
•0 to 15
• 0: The alarm is suppressed.
• 1: The alarm is detected by the system. No notification is issued.
• 2: Reserved for block alarms.
• 3-7: Informative alarm with increasing priority,
3: Low priority, 7: High priority
• 8-15: Critical alarm with increasing priority,
8: Low priority, 15: High priority
Factory setting:
0
High Limit/HI_LIM
Entry
Index: 28
Data type: float
Access: auto, man, OOS
Enter upper limit value.
Input range:
Range and units of Output Scale/OUT_SCALE (→ ä 96)
Factory setting:
+INF
Low Priority/LO_PRI
Entry
Index: 29
Data type: unsigned8
Access: auto, man, OOS
Specify how the system should react if the Low Limit/LO_LIM limit value (→ ä 100) is
undershot.
Input range:
•0 to 15
• 0: The alarm is suppressed.
• 1: The alarm is detected by the system. No notification is issued.
• 2: Reserved for block alarms.
• 3-7: Informative alarm with increasing priority,
3: Low priority, 7: High priority
• 8-15: Critical alarm with increasing priority,
8: Low priority, 15: High priority
Factory setting:
0
Low Limit/LO_LIM
Entry
Index: 30
Data type: float
Access: auto, man, OOS
Enter lower limit value.
Input range:
Range and units of Output Scale/OUT_SCALE (→ ä
96)
Factory setting:
–INF
Analog Input Block
Parameter Description