Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 149
FULL CALIB. (004)
Entry
Enter the height, volume or mass value for the upper calibration point (container full).
The container is either completely or almost full. By entering a value for this parameter,
you assign a height, volume or mass value to the pressure present at the device. The unit
is selected via the OUTPUT UNIT parameter ( ä 148).
Prerequisite:
CALIBRATION MODE = Wet
!
Note!
For this parameter, the local operation shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
EMPTY CALIB. (010)
Entry
Enter the level, volume, mass or percentage value for the lower calibration point (empty
container).
The values entered for the EMPTY CALIB. and EMPTY PRESSURE parameters form the
pressure-level value pair for the lower calibration point. The unit is selected via the
OUTPUT UNIT parameter ( ä 148).
Prerequisite:
CALIBRATION MODE = Dry
Factory setting:
0.0
EMPTY PRESSURE (011)
Entry
Enter the pressure value for the lower calibration point (container empty).
See also EMPTY CALIB.
Prerequisite:
CALIBRATION MODE = Dry
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter the height, volume, mass or percentage value for the upper calibration point
(container full).
The values entered for the FULL CALIB. and FULL PRESSURE parameters form the
pressure-level value pair for the upper calibration point. The unit is selected via the
OUTPUT UNIT parameter ( ä 148).
Prerequisite:
CALIBRATION MODE = Dry
Factory setting:
100.0
FULL PRESSURE (005)
Entry
Enter the pressure value for the upper calibration point (container full).
See also FULL CALIB.
Prerequisite:
CALIBRATION MODE = Dry
Factory setting:
100.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the local
operation, measured value and OUT value of the Analog Input Block react to a change in
the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 8: OPERATING MENU SETTINGS BASIC SETUP "Level",
LEVEL SELECTION "Level easy pressure"
Parameter name Description