Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 163
CUST. UNIT FACT. V (607)
Entry
Enter the conversion factor for a customer-specific volume unit.
The conversion factor must be entered in relation to the SI unit "m
3
".
See also CUSTOMER UNIT V.
Prerequisite:
LIN. MEASURAND = Volume, UNIT VOLUME = User unit
Example:
You want the measured value to be displayed in "buckets".
MEASURED VALUE = 0.01 m3 i 1 bucket
Entry CUSTOMER UNIT V: bucket
Entry CUST. UNIT FACT. V: 100
Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
TANK VOLUME (858)
Entry
Enter the tank volume.
Prerequisite:
LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Factory setting:
1.0 m
3
HEIGHT UNIT (708)
Selection
Select the level unit.
Prerequisite:
LIN. MEASURAND = % (level), CALIBRATION MODE = Dry
Options:
•mm
•dm
•cm
•m
•inch
•ft
•User unit, see also the following parameter descriptions for CUSTOMER UNIT H
and CUST. UNIT. FACT. H.
Factory setting:
m
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST. UNIT. FACT. H.
Prerequisite:
LIN. MEASURAND = % (level), CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
Table 11: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Linear"