Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 173
CUSTOMER UNIT M (704)
Entry
Enter text (unit) for customer-specific mass unit.
You can enter a maximum of eight alphanumeric characters here. See also CUST.
UNIT. FACT. M.
Prerequisite:
COMB. MEASURAND = Height and mass, MASS UNIT = User unit
COMB. MEASURAND = %-height and mass, MASS UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. M (703)
Entry
Enter the conversion factor for a customer-specific mass unit.
The conversion factor must be entered in relation to the SI unit "kg". See also
CUSTOMER UNIT M.
Prerequisite:
COMB. MEASURAND = Height and mass, MASS UNIT = User unit
COMB. MEASURAND = %-height and mass, MASS UNIT = User unit
Example:
You want the measured value to be displayed in "buckets".
MEASURED VALUE = 10 kg i 1 bucket
Entry CUSTOMER UNIT M: bucket
Entry CUST. UNIT FACT. M: 0.1
Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
LEVEL MIN (755)
Entry
Enter the minimum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum level to be expected, the more
accurate the measurement result.
Factory setting:
0.0
LEVEL MAX (712)
Entry
Enter the maximum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the maximum level to be expected, the more
accurate the measurement result.
Factory setting:
100.0
Table 13: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Height linearized"
Parameter name Description