Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 175
DENSITY UNIT (812)
Selection
Select the density unit.
Prerequisite:
• COMB. MEASURAND = %-height and %, CALIBRATION MODE = Dry
•COMB. MEASURAND = %-height and volume, CALIBRATION MODE = Dry
•COMB. MEASURAND = %-height and mass, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and %, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and mass, CALIBRATION MODE = Dry
Options:
•g/cm
3
•kg/dm
3
•kg/m
3
• US lb/in
3
• US lb/ft
3
Factory setting:
kg/dm
3
ADJUST DENSITY (316)
Entry
Enter the density of the fluid.
Prerequisite:
• COMB. MEASURAND = %-height and %, CALIBRATION MODE = Dry
•COMB. MEASURAND = %-height and volume, CALIBRATION MODE = Dry
•COMB. MEASURAND = %-height and mass, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and %, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and mass, CALIBRATION MODE = Dry
Factory setting:
1.0
HEIGHT UNIT (708)
Selection
Select the level unit.
Prerequisite:
•COMB. MEASURAND = %-height and volume, CALIBRATION MODE = Dry
•COMB. MEASURAND = %-height and mass, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-height and %, CALIBRATION MODE = Dry
Options:
•mm
•dm
•cm
•m
•inch
•ft
•User unit, → see also the following parameter descriptions for CUSTOMER UNIT H
and CUST. UNIT. FACT. H.
Factory setting:
m
Table 13: OPERATING MENU → SETTINGS → BASIC SETUP "Level", LEVEL MODE "Height linearized"
Parameter name Description