Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
176 Endress+Hauser
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST. UNIT. FACT. H.
Prerequisite:
COMB. MEASURAND = %-height and volume, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
COMB. MEASURAND = %-height and mass, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
COMB. MEASURAND = %-height and %, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter the conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
See also CUSTOMER UNIT H.
Prerequisite:
COMB. MEASURAND = %-height and volume, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
COMB. MEASURAND = %-height and mass, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
COMB. MEASURAND = %-height and %, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
Example:
You want the measured value to be displayed in "PU" (PU: packing unit).
MEASURED VALUE = 0.5 m i 1 PU
Entry CUSTOMER UNIT H: PU
Entry CUST. UNIT FACT. H: 2
Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
100% POINT (813)
Entry
Enter the level value for the 100% point.
Prerequisite:
COMB. MEASURAND = %-height and volume, CALIBRATION MODE = Dry
COMB. MEASURAND = %-height and mass, CALIBRATION MODE = Dry
COMB. MEASURAND = %-height and %, CALIBRATION MODE = Dry
Example:
The 100 %-point should correspond to 4 m (13 ft).
Select the "m" unit via the HEIGHT UNIT parameter.
Enter the value "4" for this parameter (100% POINT).
Factory setting:
1.0
Table 13: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL MODE "Height linearized"