Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 179
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The digital output
value of the Analog Input Block OUT no longer displays the same value as the local
operation or the MEASURED VALUE. The device has to be recalibrated if the measuring
mode is changed. ä 129, Section 10 "Flow measurement (via local operation and
FieldCare)".
Options:
Pressure
Level
Deltabar S: Flow
Factory setting:
Pressure
PRESS. ENG. UNIT (060)
Selection
Select the pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
mbar, bar
mmH2O, mH2O, inH2O, ftH2O
Pa, hPa, kPa, MPa
•psi
mmHg, inHg
•Torr
•g/cm
2
, kg/cm
2
•lb/ft
2
•atm
•gf/cm
2
, kgf/cm
2
•User unit, see also the following parameter descriptions for CUSTOMER UNIT P
and CUST. UNIT. FACT. P
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order
specifications
CUSTOMER UNIT P (075)
Entry
Enter text (unit) for customer-specific pressure unit.
You can enter a maximum of eight alphanumeric characters here. See also CUST.
UNIT. FACT. P
Prerequisite:
PRESS. ENG. UNIT = User unit
!
Note!
Only the first five characters are shown on the local operation. For example, if the
customer-specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation.
The maximum number of characters in the counter is again limited to five. For example if
the customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed.
FieldCare accepts units with eight characters at most. The slash counts as one character.
Factory setting:
_ _ _ _ _ _ _ _
Table 14: OPERATING MENU SETTINGS BASIC SETUP "Flow"
Parameter name Description