Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
180 Endress+Hauser
CUST. UNIT FACT. P (317)
Entry
Enter the conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". See also
CUSTOMER UNIT P.
Prerequisite:
PRESS. ENG. UNIT = User unit
Example:
You want the measured value to be displayed in "PU" (PU: packing unit).
MEASURED VALUE =10000 Pa i 1 PU
Entry CUSTOMER UNIT P: PU
Entry CUST. UNIT FACT. P: 0.0001
Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
FLOW-MEAS. TYPE (640)
Selection
Select the flow type.
Options:
Volume operat. cond. (volume under operating conditions)
Gas norm. cond. (norm volume under norm conditions in Europe: 1013.25 mbar and
273.15 K (0 °C))
Gas std. cond. (standard volume under standard conditions in USA: 1013.25 mbar
(14.7 psi) and 288.15 K (15 °C/59 °F))
•Mass
Factory setting:
Volume operat. cond.
UNIT FLOW (391)
Selection
Select volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
FLOW-MEAS. TYPE = Volume operat. cond.
Options:
m3/s, m3/min, m3/h, m3/day
l/s, l/min, l/h
hl/s, hl/min, hl/day
ft3/s, ft3/min, ft3/h, ft3/day
ACFS, ACFM, ACFH, ACFD
•ozf/s, ozf/min
US Gal/s, US Gal/min, US Gal/h, US Gal/day
Imp. Gal/s, Imp. Gal/min, Imp. Gal/h
bbl/s, bbl/min, bbl/h, bbl/day
•User unit, see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT. FACT. F
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
m
3
/s
Table 14: OPERATING MENU SETTINGS BASIC SETUP "Flow"
Parameter name Description