Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
180 Endress+Hauser
CUST. UNIT FACT. P (317)
Entry
Enter the conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". → See also
CUSTOMER UNIT P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE =10000 Pa i 1 PU
– Entry CUSTOMER UNIT P: PU
– Entry CUST. UNIT FACT. P: 0.0001
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
FLOW-MEAS. TYPE (640)
Selection
Select the flow type.
Options:
• Volume operat. cond. (volume under operating conditions)
• Gas norm. cond. (norm volume under norm conditions in Europe: 1013.25 mbar and
273.15 K (0 °C))
• Gas std. cond. (standard volume under standard conditions in USA: 1013.25 mbar
(14.7 psi) and 288.15 K (15 °C/59 °F))
•Mass
Factory setting:
Volume operat. cond.
UNIT FLOW (391)
Selection
Select volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = Volume operat. cond.
Options:
• m3/s, m3/min, m3/h, m3/day
• l/s, l/min, l/h
• hl/s, hl/min, hl/day
• ft3/s, ft3/min, ft3/h, ft3/day
• ACFS, ACFM, ACFH, ACFD
•ozf/s, ozf/min
• US Gal/s, US Gal/min, US Gal/h, US Gal/day
• Imp. Gal/s, Imp. Gal/min, Imp. Gal/h
• bbl/s, bbl/min, bbl/h, bbl/day
•User unit, → see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT. FACT. F
!
Note!
Following a change in the unit, the digital output value of the Analog Input value OUT
and the local operation or the MEASURED VALUE no longer display the same value.
→ See also parameter descriptions for XD SCALE, OUT SCALE and OUT value.
Factory setting:
m
3
/s
Table 14: OPERATING MENU → SETTINGS → BASIC SETUP "Flow"
Parameter name Description