Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
188 Endress+Hauser
EDITOR TABLE
Entry ("Manual" edit mode)
LINE-NUMB (549)
Y-VAL. (551)
–X-VAL. (550)
Enter the table in the "Manual" editing mode.
A linearization table must have at least 2 points and may not have more than 32 points. A
point consists of an index, X-value and Y-value. The container neither has to be filled nor
emptied for this editing mode.
Example: Enter point for LEVEL MODE = Pressure linearized
LINE-NUMB: Confirm value displayed.
X-VAL.: enter pressure value.
Y-VAL.: depending on the setting in the LINd. MEASURAND parameter, enter the
related volume, mass or % value.
Example: Enter point for LEVEL MODE = Height linearized
LINE-NUMB: Confirm value displayed.
X-VAL.: The hydrostatic pressure present is measured. Depending on the setting in the
COMB. MEASURAND parameter, enter a level value or % value.
Y-VAL.: depending on the setting in the COMB. MEASURAND parameter, enter the
related volume, mass or % value.
Factory setting:
LINE-NUMB = 1, X-VAL. = 0.0, Y-VAL. = 0.0
EDITOR TABLE (770)
Selection
Select the function for the editor table.
Options:
Next point: enter next point.
Last input point: skip back to previous point to correct a mistake for example.
Accept input table: save editor table as measuring table. This overwrites the old
measuring table.
Abort: save values entered up to this point for the editor table and display next
parameter. The editor table is not activated as a measuring table.
Insert point: see example below.
Delete point: the current point is deleted. See example below.
Example: Add point, in this case between the 4th and 5th point for example
Select point 5 via the EDITOR TABLE/LINE NUMB parameter.
Confirm current X and Y values with Enter.
Using the EDITOR TABLE (770) parameter, select the option "Insert point".
Point 5 is displayed for the EDITOR TABLE/LINE NUMB parameter. Enter new values
for the X-VAL and Y-VAL parameters.
Example: Delete point, in this case the 5th point for example
Select point 5 via the EDITOR TABLE/LINE NUMB parameter.
Using the EDITOR TABLE (770) parameter, select the option "Delete point".
The 5th point is deleted. All of the following points are pushed up one number i.e.
following deletion, the 6th point becomes Point 5.
Factory setting:
Next point
MEASURING TABLE (549)
Display
A point of the linearization table saved (measuring table) appears on the display.
The parameter first displays the first point of the linearization table. By entering a line
number, you can directly display the corresponding point in the linearization table.
MEASURING TABLE (717)
Selection
Select the function for the measuring table.
Options:
Next point: view next point of the measuring table.
Last input point: view previous point of the measuring table.
Abort: cancel measuring table display. Display next parameter.
Factory setting:
Next point
TANK DESCRIPTION (815)
Entry
Enter tank description. (max. 32 alphanumeric characters)
Factory setting:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Table 18: GROUP SELECTION OPERATING MENU SETTINGS LINEARIZATION
– Local operation
Parameter name Description