Parameter description (Local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
190 Endress+Hauser
LIN. EDIT MODE
Selection
Select the entry mode for the linearization table.
Prerequisite:
• TABLE SELECTION = Editor table
Options:
•Manual:
The container neither has to be filled nor emptied for this entry mode. Enter the value
pairs for the linearization table.
• Semiautomatic: The container is filled or emptied in stages in this entry mode. The
device automatically records the hydrostatic pressure. The associated volume, mass or
%-value is entered.
Factory setting:
Manual
EDITOR TABLE
Selection
Select table.
Prerequisite:
• TABLE SELECTION = Editor table
Options:
• New table:
Enter a new linearization table.
•View meas. table:
View the measuring table saved and change points if necessary.
• Continue edit:
Edit an editor table that already exists.
!
Note!
FieldCare:
• If you select the "View meas. table" option, the saved measuring table is loaded in
FieldCare. Use the "Lin.-Tab." window to the view the entire table, change values if
necessary and write the modified table to the device.
• If you change a value via the X-VAL. or Y-VAL. parameters, the table in the "Lin-Tab."
window is not updated. To view the table saved in the device, this table must first be
read out of the device.
Factory setting:
New table
LINE-NUMB
Entry
Enter the line number for the linearization table. A linearization table must have at least 2
points and may not have more than 32 points.
• TABLE SELECTION = View meas. table
Via this parameter you can select the point of the linearization table which should be
displayed.
• TABLE SELECTION = Editor table
Enter a point via the LINE-NUMB, X-VAL. and Y-VAL. parameters.
→ See also this table, parameter description for LIN. EDIT MODE, X-VAL. ("Manual"
entry mode), X-VAL. ("Semiautomatic" entry mode) and Y-VAL.
!
Note!
In FieldCare, you can enter a complete linearization table in one go, and view it, via the
"Lin.-Tab." window.
X-VAL. ("Manual" entry
mode)
Entry
Enter the pressure value for the linearization table.
→ See also LIN. EDIT MODE, LINE-NUMB and Y-VAL.
Prerequisite:
• TABLE SELECTION = Editor table
X-VAL. ("Semiautomatic"
entry mode)
Display
In the "Semiautomatic" entry mode, the container is filled or emptied in stages. The
X-VAL. displays the measured hydrostatic pressure.
Prerequisite:
• TABLE SELECTION = Editor table
FieldCare
The X-VAL. is saved by confirming the Y-value.
→ See also LIN. EDIT MODE, LINE-NUMB and Y-VAL.
Table 19: MANUFACTURER VIEW → OPERATING MENU → SETTINGS → LINEARIZATION – FieldCare
Parameter name Description