Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (Local operation and FieldCare)
Endress+Hauser 197
CONFIG RECORDER (352)
Display
Displays the configuration counter.
This counter is increased by one with each change to a parameter or group. The counter
counts up to 65535 and then starts again at zero. Changes in the parameters of the
DISPLAY function group do not increase the counter.
PCB TEMPERATURE (357)
Display
Displays the measured temperature of the main electronics.
ALLOWED MIN. TEMP
(358)
Display
Displays the lower temperature limit of the main electronics.
ALLOWED MAX. TEMP
(359)
Display
Displays the upper temperature limit of the main electronics.
DIP STATUS (363)
Display
Displays the status of DIP switch 1 on the electronic insert.
You can lock or unlock parameters relevant to the measured value with DIP switch 1. If
operation is locked by means of the INSERT PIN No. parameter, you can only unlock
operation again by means of this parameter. (INSERT PIN NO, see Page 205.)
See also Operating Instructions for Deltabar S (BA00301P), Cerabar S (BA00302P) or
Deltapilot S (BA00372P), "Locking/unlocking operation" section.
Display:
On (locking switched on)
Off (locking switched off)
Factory setting:
Off (locking switched off)
Table 24: OPERATING MENU TRANSMITTER INFO PROCESS CONNECTION
Parameter name Description
Pmax PROC. CONN. (570)
Entry
For entering and displaying the maximum permitted pressure of the process connection.
Factory setting:
In accordance with nameplate data (See also Operating Instructions for Deltabar S (
BA00301P), Cerabar S (BA00302P) or Deltapilot S (BA00372P), "Nameplates" section)
PROC. CONN. TYPE (482)
Selection
For selecting and displaying the process connection type.
Options:
•Not used
•Unknown
Special
•Oval flange
•Thread female
•Thread male
•Flange
•Remote seal
Table 23: OPERATING MENU TRANSMITTER INFO TRANSMITTER DATA