Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Troubleshooting
Endress+Hauser 211
116 (W116) Warning
C
C>Download error,
repeat download
17 0 – The file is defect. – Use another file. 37
– During the download, the data
are not correctly transmitted to
the processor, e.g. because of
open cable connections, spikes
(ripple) on the supply voltage or
electromagnetic effects.
– Check cable connection PC –
transmitter.
– Block off electromagnetic effects
or eliminate sources of
disturbance.
– Perform reset (code 7864) and
recalibrate the device.
–Repeat download.
120 (E120) Error
C
C>Sensor low pressure 17 0 – Pressure too low. – Increase pressure until message
disappears.
31
– Sensor defect. – Replace sensor.
121 (A121) Alarm
B
B>Checksum error in
factory segment of
EEPROM
23 11 – Main electronics defect. – Replace main electronics. 5
122 (A122) Alarm
B
B>Sensor not connected 20 5 – Cable connection sensor –main
electronics disconnected.
– Check cable connection and
repair if necessary.
14
– Electromagnetic effects are
greater than specifications in the
technical data.
→ See Technical Information
TI00382P (Deltabar S),
TI00383P (Cerabar S) or
TI00416P (Deltapilot S).
– Block off electromagnetic effects
or eliminate source of
disturbance.
– Main electronics defect. – Replace main electronics.
– Sensor defect. – Replace sensor.
130 (A130) Alarm
B
B>EEPROM is defect. 23 11 – Main electronics defect. – Replace main electronics. 10
131 (A131) Alarm
B
B>Checksum error in
EEPROM: min/max
segment
23 11 – Main electronics defect. – Replace main electronics. 9
132 (A132) Alarm
B
B>Checksum error in
totalizer EEPROM
23 11 – Main electronics defect. – Replace main electronics. 7
133 (A133) Alarm
B
B>Checksum error in
History EEPROM
23 11 – An error occurred when
writing.
– Perform reset (code 7864) and
recalibrate the device.
8
– Main electronics defect. – Replace main electronics.
134 (W134) Warning
C
C>EEPROM lifetime
WARNING
17 0 – Writing too often to EEPROM. – Reduce write accessing to
EEPROM.
55
135 (A135) Alarm
B
B>Checksum error in
EEPROM FF segment
23 11 – Main electronics defect. – Replace main electronics. 10
602 (W602) Warning
C
C>Linearization curve
not monoton
19 7 – The linearization table is not
monotonic increasing.
– Add to or correct linearization
table. Then accept linearization
table again.
57
604 (W604) Warning
C
C>linearization table
invalid. Min. 2 points
19 7 – The linearization table consists
of less than 2 points.
– Add to linearization table.
Accept linearization table again
if necessary.
58
613 (W613) Warning
I
I>Simulation is active 17 3 – Simulation is switched on, i.e.
the device is not measuring at
present.
– Switch off simulation. 60
Code Error
type/
NA 64
Message/description XD_
ERROR
Value
BLOCK_
ERROR
Bit
Cause Measure Prio-
rity