Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 43
Restart/RESTART
Selection
Index: 16
Data type: unsigned8
Access: r, w
Select the reset mode.
Options:
• ENP_RESTART: A restart is needed to accept the ENP configuration changes.
• Run: Standard operating mode
• Resource: This mode is not supported by Endress+Hauser.
• Defaults: The device data and the links of the function blocks are reset to the factory
settings. The manufacturer-specific parameters of the Transducer Block are not reset to the
factory settings.
→ See also Operating Instructions BA00301P (Deltabar S) or BA00302P (Cerabar S) or
BA00372P (Deltapilot S), "Factory setting" (reset) section.
• Processor: Warm start of device, processor restart.
• Factory: The links of the function blocks, all FF-specific and resettable manufacturer-
specific parameters are reset to the factory setting.
Features/FEATURES
Display
Index: 17
Data type: bit string
Access: read only
Displays the additional functions supported by the device. → See also this Table, Feature
Selection/FEATURE_SEL parameter description.
Feature Selection/
FEATURE_SEL
Selection
Index: 18
Data type: bit string
Access: auto, OOS
Select the additional device functions. The additional functions that the device supports are
displayed in the Features/FEATURES parameter (→ ä 43).
Cycle Type/
CYCLE_TYPE
Display
Index: 19
Data type: bit string
Access: read only
Displays the block execution methods supported by the device. → See also this Table, Cycle
Selection/CYCLE_SEL parameter description.
Cycle Selection/
CYCLE_SEL
Display
Index: 20
Data type: bit string
Access: auto, OOS
Displays the block execution method used by the fieldbus host system. The block execution
method is selected by the fieldbus host system.
Possibilities:
• Scheduled: cyclical block execution method
• Block execution: sequential block execution method
Minimum Cycle Time/
MIN_CYCLE_T
Display
Index: 21
Data type: Unsigned32
Access: read only
Displays the shortest MACROCYCLE supported by the device.
Factory setting:
3200
1
/
32
ms (≅ 100 ms)
Memory Size/
MEMORY_SIZE
Display
Index: 22
Data type: DS-69
Access: read only
Displays the available configuration memory in kilobytes. This parameter is not supported by
Deltabar S, Cerabar S and Deltapilot S.
Nonvolatile Cycle Time/
NV_CYCLE_T
Display
Index: 23
Data type: Unsigned32
Access: read only
Displays the time interval for which the dynamic device parameters are stored in the
nonvolatile memory. Since the Cerabar S, Deltabar S and Deltapilot S units do not store the
dynamic device parameters in the nonvolatile memory, the parameter always displays the
value 0
1
/
32
ms.
Resource Block
Parameter Description