Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 67
Zero Point/
ZERO_POSITION
Entry
Index: 61
Data type: float
Access: auto, OOS
Enter the value for level offset.
If the measurement should not start at the mounting location of the device, e.g. for containers
with a sump, carry out zero point shift (level offset).
Prerequisite:
Calibration Mode/CALIBRATION_MODE = Dry
Factory setting:
0.0
P01-PMP75xxx-19-xx-xx-xx-001
Fig. 17: Zero point shift
1 Device is mounted above the level lower-range value: a positive value has to be
entered for the LEVEL_ADJUST_MODE/ZERO POINT parameter.
2 Device is mounted below the level lower-range value: a negative value has to be
entered for the LEVEL_ADJUST_MODE/ZERO POINT parameter.
Empty Calib./
EMPTY_CALIBRATION
Entry
Index: 62
Data type: float
Access: auto, OOS
Enter the level value for the lower calibration point (container empty).
The container is either empty or part full. By entering a value for this parameter, you are
assigning a level value to the pressure present at the device.
see also Empty Pressure Level Easy/EMPTY_PRESSURE_EASY.
Prerequisite:
Calibration Mode/CALIBRATION_MODE = Wet
!
Note!
For this parameter, the local operation shows the level value to be entered and the pressure
present at the device. In order for the level value to be saved together with the pressure
present at the device, the entry field for the level value must first be activated using the "+"-
or "–" key before confirming with the "E" key. This applies also if the level value is to remain
unchanged.
Factory setting:
0.0
Full Calib./
FULL_CALIBRATION
Entry
Index: 63
Data type: float
Access: auto, OOS
Enter the level value for the upper calibration point (container full).
The container is either completely or almost full. By entering a value for this parameter, you
are assigning a level value to the pressure present at the device.
See also Full Pressure Level Easy/FULL_PRESSURE_EASY.
Prerequisite:
Calibration Mode/CALIBRATION_MODE = Wet
!
Note!
For this parameter, the local operation shows the level value to be entered and the pressure
present at the device. In order for the level value to be saved together with the pressure
present at the device, the entry field for the level value must first be activated using the "+"-
or "–" key before confirming with the "E" key. This applies also if the level value is to remain
unchanged.
Factory setting:
100.0
Pressure Transducer Block
Parameter Description