Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
66 Endress+Hauser
Calibration Mode/
CALIBRATION_MODE
Selection
Index: 59
Data type: unsigned8
Access: auto, OOS
Select the calibration mode.
Options:
• Wet: option without a function
•Dry
Dry calibration is a theoretical calibration which you can carry out even if the device is not
mounted or the container is empty.
– For the "Level" measured variable, the density of the fluid (→ ä 66: Adjust Density/
ADJUST_DENSITY) must be entered.
– For the "Volume" measured variable, the density of the fluid and the tank volume and
tank height must be entered (→ ä 66: Adjust Density/ADJUST_DENSITY,
→ ä 68: Tank Volume/TANK_VOLUME and → ä 68: Tank Height/
TANK_HEIGHT).
– For the "Mass" measured variable, the tank volume and tank height must be entered
(→ ä 68, Tank Volume/TANK_VOLUME and → ä 68: Tank Height/
TANK_HEIGHT). In the event of a zero point shift (level offset), the density also has to
be entered (→ ä 66, Adjust Density/ADJUST_DENSITY).
– For the "%" measured variable, the density of the fluid has to be entered and a level also
has to be assigned to the 100 % point (→ ä 66: Adjust Density/ADJUST_DENSITY
and → ä 68: 100% Point/HUNDRED_PERCENT_VALUE).
If the measurement should not start at the mounting location of the device, a level offset
must be entered (→ ä 67: Zero Point/ZERO_POSITION).
Factory setting:
Wet
Adjust Density/
ADJUST_DENSITY
Entry
Index: 60
Data type: float
Access: auto, OOS
Enter the density of the fluid.
Prerequisite:
• Comb. Measurand/COMBINED_MEASURAND = %-height and %,
Calibration Mode/CALIBRATION_MODE= Dry
• Comb. Measurand/COMBINED_MEASURAND = %-height and volume,
Calibration Mode/CALIBRATION_MODE= Dry
• Comb. Measurand/COMBINED_MEASURAND = %-height and mass,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = Height and %,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = Height and volume,
Calibration Mode/CALIBRATION_MODE = Dry
• Comb. Measurand/COMBINED_MEASURAND = Height and mass,
Calibration Mode/CALIBRATION_MODE = Dry
– Comb. Measurand = COMBINED_MEASURAND
– Calibration Mode = CALIBRATION_MODE
Factory setting:
1.0
Pressure Transducer Block
Parameter Description