Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
82 Endress+Hauser
7.3.4 DP Flow Transducer Block (only Deltabar S)
DP Flow Transducer Block
Parameter Description
Device Dialog/
DEVICE_DIALOG
Display
Index: 11
Data type: unsigned8
Access: read only
If the configuration is not suitable, this parameter displays a message saying that a
configuration error is present. The message can indicate which parameter was incorrectly
configured.
Insert Pin No./
SW_LOCK
Entry
Index: 12
Data type: unsigned16
Access: read, write
For entering a code to lock or unlock operation.
!
Hinweis!
The symbol on the on-site display indicates that operation is locked. Parameters which
refer to how the display appears, e.g. LANGUAGE and DISPLAY_CONTRAST can still be
altered.
If operation is locked by means of the DIP-switch, cou can only unlock operation again by
means of the DIP-switch. If operation is locked by means of remote operation, you can
only unlock operation again by means of remote operation.
See also Operating Instructions BA00301P (Deltabar S) or BA00302P (Cerabar S) oder
BA00372P (Deltapilot S) Chapter "Locking/unlocking operation".
Options:
Lock: enter a number between 0...9999 which is 100.
Unlock: enter number 100.
Factory setting:
100
Status Locking/
STATUS_LOCKING
Index: 13
Data type: unsigned8
Access: read only
Shows the actual locking status of the device or conditions that can cause the locking.
(Hardware locking, Software locking)
Flow-Meas. Type/
FLOW_MEAS_TYPE
Selection
Index: 14
Data type: unsigned8
Access: read, write, OOS
Select the flow type.
Prerequisite:
Deltabar S differential pressure transmitter
Options:
Volume operat. cond. (volume under operating conditions)
Volume norm. cond. (norm volume under norm conditions in Europe: 1013.25 mbar and
273.15 K (0 °C))
Volume std. cond. (standard volume under standard conditions in USA: 1013.25 mbar
(14.7 psi) and 288.15 K (15 °C/59 °F))
Mass p. cond. (mass under operating conditions)
Factory setting:
Volume operat. cond.
Suppressed Flow/
SUPPRESSED_FLOW
Display
Index: 15
Data type: Float
Access: read only
Displays the current flow. Depending on the flow mode selected (
Flow-Meas. Type/
FLOW_MEAS_TYPE), a volume flow, mass flow, standard volume flow or corrected volume
flow is
displayed.