Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 81
Download Select/
DOWNLOAD_
SELECTION
Display
Index: 49
Data type: unsigned8
Access: auto, OOS
Select download function from HistoROM to device. The option selected has no effect on an
upload from the device to the HistoROM.
Prerequisite:
•A HistoROM
®
/M-DAT is attached to the electronic insert (HistoROM AVAIL. = Yes)
Options:
Configuration copy: With this option, all parameters apart from the TRANSMITTER
SERIAL No, DEVICE DESIGNATION, CUST. TAG NUMBER, LONG TAG NUMBER,
ADDITIONAL INFO., BUS ADDRESS and the parameters of the POSITION
ADJUSTMENT and PROCESS CONNECTION group are overwritten.
Device replacement: With this option, all parameters except for TRANSMITTER SERIAL
No, DEVICE DESIGNATION and the parameters of the POSITION ADJUSTMENT and
PROCESS CONNECTION group are overwritten.
Electronics replace: With this option, all parameters except for the parameters of the
POSITION ADJUSTMENT group are overwritten.
Factory setting:
Configuration copy (if HistoROM
®
/M-DAT is attached to the electronic insert)
HistoROM Control/
HISTOROM_CONTROL
Selection
Index: 50
Data type: unsigned8
Access: auto, OOS
For selecting the direction for copying the data.
See also Operating Instructions BA00301P (Deltabar S) or BA00302P (Cerabar S) or
BA00372P (Deltapilot S), "HistoROM
®
/M-DAT (optional)" section.
Prerequisite:
•A HistoROM
®
/M-DAT is attached to the electronic insert
(HistoROM Avail./HISTOROM_AVAILABLE = Yes)
Options:
Abort
•HistoROM Device
Device HistoROM
Factory setting:
Abort (if HistoROM
®
/M-DAT is attached to the electronic insert)
Press. Eng. Unit/
PRESSURE_UNIT
Display
Index: 51
Data type: unsigned16
Access: read only
Displays the pressure unit selected.
The pressure unit is selected via the Calibration Units/CAL_UNIT parameter ( ä 54) in
the Pressure Transducer Block.
Temp. Eng. Unit/
TEMPERATURE_UNIT
Display
Index: 52
Data type: unsigned16
Access: read only
Displays the temperature unit selected.
You can select the temperature unit by means of the Secondary Value Unit/
SECONDARY_VALUE_UNIT parameter ( ä 56) in the Pressure Transducer Block.
Inp. Press. Ivers/
INPUT_PRESSURE_
INVERSION
Index: 53
Data type: unsigned8
Access: auto, OOS
(only with Service Code)
Internal service parameter
Service Transducer Block
Parameter Description