Parameter description (FF configuration program) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
90 Endress+Hauser
Simulation Mode/
SIMULATION_MODE
Selection
Index: 13
Data type: unsigned8
Access: auto, OOS
Switch on simulation and select simulation type.
Any simulation running is switched off if the measuring mode or level mode is changed.
Options:
•None
Pressure
Flow (only differential pressure transmitter)
Level
Tank content
Alarm/warning
P01-xMD7xxxx-05-xx-xx-en-004
Factory setting:
None
Units Index/
SCALE_OUT_UNITS_
INDEX
Display
Index: 14
Data type: unsigned16
Access: read only
Displays the unit selected via the Scale Out/SCALE_OUT parameter ( ä 58) in the
Pressure Transducer Block.
Simulated Value/
SIMULATED_VALUE
Entry
Index: 15
Data type: float
Access: auto, OOS
Enter the simulation value.
Prerequisite:
Simulation Mode/SIMULATION_MODE = Pressure, flow, level or tank content.
Sim. Error No./
SIMULATION_ERROR_
NUMBER
Entry
Index: 16
Data type: unsigned16
Access: auto, OOS
Enter the message number for simulation.
See also these Operating Instructions, Section 12.1 "Messages", "Code" table column.
Prerequisite:
Simulation Mode/SIMULATION_MODE = Alarm/warning
Factory setting:
613 (simulation active)
Alarm Status/
ALARM_STATUS
Display
Index: 17
Data type: unsigned16
Access: read only
Displays the current messages present. If two or more messages are present, the message
with the highest priority is shown on the display. See also these Operating Instructions,
Section 12.1 "Messages" and Section 12.3 "Confirming messages".
Last Diag. Code/
LAST_DIAGNOSTIC_
CODE
Display
Index: 18
Data type: unsigned16
Access: read only
Displays the last error that occurred and was eliminated.
!
Note!
The message displayed here can be deleted by means of the Reset All Alarms/RESET_
ALL_ALARMS parameter.
Diagnostic Transducer Block
Parameter Description
P
PV
Simulation value pressure
Transducer Block
Simulation value level
Simulation value tank content
Simulationvalue flow
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim