Temperature head transmitter 6 Commissioning
Endress+Hauser 45
Function group: BASIC CALIBRATION
Type of sensor
•V2H0
Entry of sensor used:
Sensor type Range start Range end value
-10..75 mV -10 mV 75 mV
10..400 Ohm 10
Ω 400 Ω
10..2000 Ohm 10 Ω 2000 Ω
Pt100 DIN -200 °C (-328 °F) 850 °C (1562 °F)
Pt100 JIS -200 °C (-328 °F) 649 °C (482 °F)
Pt500 -200 °C (-328 °F) 250 °C (482 °F)
Pt1000 -200 °C (-328 °F) 250 °C (482 °F)
Ni100 -60 °C (-76 °F) 180 °C (356 °F)
Ni500 -60 °C (-76 °F 150 °C (302 °F)
Ni1000 -60 °C (-76 °F 150 °C (302 °F)
Polynom RTD -270 °C (-454 °F) 2500 °C (4532 °F)
Type B 0 °C (32 °F) 1820 °C (3308 °F)
Type C 0 °C (32 °F) 2320 °C (4208 °F)
Type D 0 °C (32 °F) 2495 °C (4523 °F)
Type E -270 °C (-454 °F) 1000 °C (1832 °F)
Type J -210 °C (-346 °F) 1200 °C (2192 °F)
Type K -270 °C (-454 °F) 1372 °C (2501 °F)
Type L -200 °C (-328 °F) 900 °C (1652 °F)
Type N -270 °C (-454 °F) 1300 °C (2372 °F)
Type R -50 °C (-58 °F) 1768 °C (3214 °F)
Type S -50 °C (-58 °F) 1768 °C (3214 °F)
Type T -270 °C (-454 °F) 400 °C (752 °F)
Type U -200 °C (-328 °F) 600 °C (1112 °F)
Polynom TC -270 °C (-454 °F) 2500 °C (4532 °F)
Pt100 DIN
Temp.Compensation
•V2H1
Selection of temperature compensation of the cold junction when using
customer specific linearisation of the TC polynom
Input:
None, Type B, Type C, Type D, Type E, Type J, Type K, Type L, Type N,
Type R, Type S, Type T, Type U
None
Unit meas. value
•V2H2
Enter engineering units.
Entry: °C
°F
K
°C
Current output
•V2H3
Enter standard (4-20 mA) or inverse (20-4 mA) current output signal.
Entry: 4-20 mA
20 - 4 mA
4-20 mA
Value for 4 mA
•V2H4
Entry: For limits see unit function SENSOR TYPE.
0 °C
Value for 20 mA
•V2H5
Entry: For limits see unit function SENSOR TYPE.
100 °C
Connection
•V2H6
•
3
33
3 RTD connection
Entry of RTD connection mode
Entry: 2 wire
3 wire
4 wire
3 wire
H
Hint!
Function field is only active on selection of resistance thermometer (RTD) in
the unit function SENSOR TYPE (V2H0)
1
.