6 Commissioning Temperature head transmitter
46 Endress+Hauser
2 wire comp.
•V2H7
Entry of cable compensation on RTD 2 wire connection.
Entry: 0.00...30.00 Ohm
0.00 Ohm
H
Hint!
Function field is only active on selection of 2 wire cable connection in unit
function CONNECTION TYPE (V2H6)
1
.
Failsafe mode
•V2H8
Entry of failure signal on sensor fracture
2
or short circuit.
Entry: max (
21,0 mA)
min (
3,6 mA)
max
Function group: LINEARIZATION
3
33
3 USER LINEARISATION
The following function fields are only active in the unit function SENSORTYPE (V2H0) on selection of
customer-specific linearisation (polynome RTD or polynome TC).
1
Coefficient X0
•V3H0
Input of first coefficient for customer-specific linearisation (polynome
4
th
grade with five coefficients), s. chapter 6.2.4
Coefficient X1
•V3H1
Input COEFFICIENT X1, s. chapter 6.2.4.
Coefficient X2
•V3H2
Input COEFFICIENT X2, s. chapter 6.2.4.
Coefficient X3
•V3H3
Input COEFFICIENT X3, s. chapter 6.2.4.
Coefficient X4
•V3H4
Input COEFFICIENT X4, s. chapter 6.2.4.
Function group: SERVICE
Error code
•V9H0
Display of actual error code.
Display: See “Application fault messages” on page 49.
0
Last diagnostic
•V9H1
Display of previous error code.
Display: See “Application fault messages” on page 49.
0
Config. changed
•V9H2
Parameter changes are done.
Display: Yes/no
No
Min primary value
•V9H3
Display the minimum process value. The process value is accepted at the
beginning of the measurement.
H
Hint!
Min. process value will be changed to the actual process value on write.
On reset to factory default, the default value is entered.
+10000