Levelflex M FMP40 FOUNDATION Fieldbus Commissioning
Endress+Hauser 59
Function "process propert" (004)
Use this funtcion to adapt the device to the filling speed in the tank. The setting impacts on an
intelligent filter.
Selection:
• standard
• fast change
• slow change
• test: no filter
Function "end of probe" (030)
Use this function to select the polarity of the probe end signal. If the probe end is uncovered or in
an insulated attachment, there is anegative probe end signal.
The signal from the probe end is positive if the attachement is grounded.
Selection:
•free
• tie down isol.
• tie down gnd.
2)
⇒
ENDRESS + HAUSER
E
+
–
Selection: standard fast change slow change test: no filter
Application: For all normal applicati-
ons, bulk solids and flu-
ids at low to medium
filling speed and suffi-
ciently large tanks.
Small tanks, primarily
with fluids, at high fil-
ling speeds.
Applications with
strong surface move-
ment, e.g. coused by
stirrer, primarily large
tanks with slow to
medium filling speed.
Shortest reaction time:
• For test purposes
•Measurement in
small tanks at high
filling speeds, if
"rapid change" set-
ting is too slow.
2-wire electronics: Dead time: 4 s
Rise time: 18 s
Dead time: 2 s
Rise time: 5 s
Dead time: 6 s
Rise time: 40 s
Dead time: 1 s
Rise time: 0 s
4-wire electronics: Dead time: 2 s
Rise time: 11 s
Dead time: 1 s
Rise time: 3 s
Dead time: 3 s
Rise time: 25 s
Dead time: 0,7 s
Rise time: 0 s
⇒
ENDRESS + HAUSER
E
+
–
2) If using a metallic centering of probe end.