Commissioning Levelflex M FMP40 FOUNDATION Fieldbus
60 Endress+Hauser
Function "probe length" (031)
Use this function to select whether the probe length was changed after factory calibration. Only then
is it necessary to enter or correct the probe length.
Selection:
• not modified
• modified
!
Note!
If "modified" was selected in the "probe length" (031) function, the probe length is defined in the
next step.
Function "probe" (032)
Use this function to select whether the probe is at the time of the commissioning uncovered or
convered. If the probe is uncovered, the Levelflex can determine the probe length automatically
"determine length" (034) function. If the probe is covered, a correct entry is required in the
"probe length" (033) function.
Selection:
• free
• covered
Function "probe length" (033)
Use this function, the probe length can be entered manually.
⇒