Levelflex M FMP40 FOUNDATION Fieldbus Commissioning
Endress+Hauser 61
Function "determine length" (034)
Use this function, the probe length can be determined automatically.
Due to the mounting conditions, the automatically determined probe length may be larger than the
actual probe (typically 20 to 30 mm longer). This has no influence on the measuring accuracy.
When entering the empty value for a linearisation, please use the "empty calibration" instead of the
automatically determined probe length.
Selection:
length ok
length short
length long
After selection "length too short" or "length too long", the calculation of the new value need approx.
10 s.
Function "empty calibr." (005)
This function is used to enter the distance from the flange (reference point of the measurement) to
the minimum level (= zero).
L00-FMP4xxxx-14-00-06-en-008.eps
ENDRESS + HAUSER
E
+
ENDRESS + HAUSER
E
+
0%
E
E = empty calibration (= zero)