4 Function group "safety settings" (01) Levelflex M
26 Endress+Hauser
MAX 110% 22mA
If the instrument is in alarm state, the output changes as follows:
• HART: MAX-Alarm 22 mA
• PROFIBUS PA: MAX-Alarm +99999
• FOUNDATION Fieldbus: MAX-Alarm +99999
hold
If the instrument is in alarm state, the last measured value is held.
user specific
If the instrument is in alarm state, the output is set to the value configured in "output on alarm"
(011) (x mA).
"
Caution!
This selection is available for HART devices only!
HART PA / FF
(110%)
(-10%)
3.6
t
[mA]
22
+99999
t
HART PA / FF
(110%)
(-10%)
3.6
t
[mA]
22
-10 %
110 %
t