8 Function group "output" (06), - "PROFIBUS param." (06), PROFIBUS PA only Levelflex M
48 Endress+Hauser
8 Function group "output" (06),
- "PROFIBUS param." (06), PROFIBUS PA only
8.1 Function "commun. address" (060), HART only
Enter the communication address for the instrument with this function.
• Standard: 0
• Multidrop: 1-15
In multidrop mode, the standard output current is 4 mA. This can be changed in the "fixed cur.
value" (064) function.
"
Caution!
This function is available for HART devices only!
8.2 Function "instrument addr." (060),
PROFIBUS PA only
The PA bus address is displayed in this field. The address is set either directly on the instrument
using DIP switches (see instrument operating instructions) or using a special SetSlaveAddress com-
mand via the bus, e.g. by the ToF Tool.
"
Caution!
This function is available for PROFIBUS PA devices only!
⇒
Display at HART and FOUNDATION Fieldbus
instrument
ENDRESS + HAUSER
E
+
–
⇒
Display at PROFIBUS PA instrument
ENDRESS + HAUSER
E
+
–
⇒
ENDRESS + HAUSER
E
+
–
⇒
ENDRESS + HAUSER
E
+
–