8 Function group "output" (06), - "PROFIBUS param." (06), PROFIBUS PA only Levelflex M
50 Endress+Hauser
8.5 Function "low output limit" (062), HART only
The output of negative level values can be suppressed with this function.
Selection:
off minimum output -10% (3.8 mA for HART)
on minimum output 0% (4 mA for HART)
"
Caution!
This user input is available for HART devices only!
8.6 Function "set unit to bus" (062), PROFIBUS PA only
•confirm
After confirming this function, the unit of the measured variable is taken over in
the AI block (PV scale -> Out scale).
This function must always be executed after changing the unit.
"
Caution!
This function is available for PROFIBUS PA devices only!