Levelflex M 11 Function group "diagnostics" (0A)
Endress+Hauser 67
11.7 Function "measured level" (0A6)
Display of measured level in the selected "distance unit" (0C5).
11.8 Function "detection window" (0A7)
(from Software 01.04.00)
Is used to switch the detection window on and off and to reset an existing detection window.
If this function is switched on, a window is defined surrounding the current level echo (typical
width: 1 to 2.5 m; depending on the application parameters).
The window always moves togehter with a rising a falling echo.
Echos beyond the limits of the window are ignored for a certain time.
Selection:
•off
•on
reset
After selection of this option, the current window is reset, the level echo is looked for in the com-
plete measuring range and a new window is defined surrounding the current level echo.
ENDRESS + HAUSER
E
+
20 mA
100%
4mA
0%
measured dist.(0A5)
measured level (0A6)
ENDRESS + HAUSER
E
+