7 Function group "extended calibr." (05) Levelflex M
42 Endress+Hauser
distance = ok
• mapping is carried out up to the currently measured echo
• The range to be suppressed is suggested in the "range of mapping (052)" function
Anyway, it is wise to carry out a mapping even in this case.
!
Note!
At free probe, the mapping should be confirmed with the choice "probe free".
dist. too small
• At the moment, an interference is being evaluated
• Therefore, a mapping is carried out including the presently measured echoes
• The range to be suppressed is suggested in the "range of mapping (052)" function
dist. too big
• This error cannot be remedied by interference echo mapping
• Check the application parameters (002), (003), (004) and "probe length" (033)
dist. unknown
If the actual distance is not known, no mapping can be carried out.
manual
A mapping is also possible by manual entry of the range to be suppressed. This entry is made in the
"range of mapping (052)" function.
"
Caution!
The range of mapping must end 0.3 m (12") before the echo of the actual level.
7.3 Function "range of mapping" (052)
This function displays the suggested range of mapping. The reference point is always the reference
point of the measurement (→ ä 1). This value can be edited by the operator.
For manual mapping, the default value is 0.3 m.
7.4 Function "start mapping" (053)
This function is used to start the interference echo mapping up to the distance given in "range of
mapping" (052).
Selection:
• off: no mapping is carried out
• on: mapping is started
⇒