Levelflex M 4 Function group "safety settings" (01)
Endress+Hauser 27
4.2 Function "output on alarm" (011), HART only
On alarm, the output current is in mA. This function is active when you selected "user specific"
in the "output on alarm" (010) function.
"
Caution!
This function is available for HART devices only!
4.3 Function "outp. echo loss" (012)
Use this function to set the output response on echo loss.
Selection:
•alarm
•hold
• ramp %/min
alarm
On echo loss, the instrument switches to alarm state after an adjustable "delay time" (014). The
output response depends on the configuration set in "output on alarm" (010).
⇓
⇒