Mounting Liquiphant FTL64 HART
12 Endress+Hauser
A0042422
2 Handling the device during transportation
5 Mounting
Mounting instructions
• Any orientation for device with short pipe up to approx. 500 mm (19.7 in)
• Vertical orientation from above for device with long pipe
• Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)
A0042329
3 Installation examples in a vessel, pipe or tank
1 Temperature spacer with gas-tight glass feedthrough for tank with insulation and/or high process
temperatures
5.1 Mounting requirements
NOTICE
Scratches or impacts damage the coated surface of the device.
‣
Ensure the device is handled properly and professionally during all mounting work.