Commissioning Liquiphant FTL64 HART
32 Endress+Hauser
9.1.1 As-delivered state
If no customized settings were ordered:
• Assign PV parameter Level limit detection (8/16 mA mode)
• MAX safety mode
• Alarm condition set to min. 3.6 mA
• DIP switch for locking in OFF position
• Bluetooth switched on
• Density range > 0.7 g/cm³
• Switching times 0.5 s when the fork is covered and 1.0 s when it is uncovered
• HART burst mode switched off
9.2 Function check
Before commissioning the measuring point, check whether the post-mounting and post-
connection checks have been performed:
•
Checklist in "Post-mounting check" section
•
Checklist in "Post-connection check" section
9.3 Switching on the device
All configuration tools provide a commissioning assistant that supports the user when
setting the most important configuration parameters (Guidance menu
Commissioning wizard).
9.4 Establishing a connection via FieldCare and
DeviceCare
9.4.1 Via HART protocol
A0046562
23 Options for remote operation via HART protocol
1 PLC (programmable logic controller)
2 Transmitter power supply unit, e.g. RN221N (with communication resistor)
3 Connection for Commubox FXA195 and Field Communicator 375, 475
4 Handheld terminal
5 Computer with operating tool (e.g. FieldCare/DeviceCare, AMS Device Manager, SIMATIC PDM)
6 Commubox FXA195 (USB)
7 Field Xpert SMT70
8 VIATOR Bluetooth modem with connecting cable
9 Device