Liquiphant FTL64 HART Diagnostics and troubleshooting
Endress+Hauser 39
10.5 Proof testing for SIL/WHG devices (optional)
3)
The "Proof test" module contains the Proof test wizard, which must be performed at
appropriate intervals in the following applications: SIL (IEC61508), WHG (German Water
Resources Act (Gesetz zur Ordnung des Wasserhaushalts)):
The wizard can be used via the operating tools (SmartBlue app, DTM).
The wizard guides the user through the entire process for creating the verification
report.
The verification report can be saved as a PDF file.
11 Diagnostics and troubleshooting
11.1 General troubleshooting
11.1.1 General errors
Device not responding
Possible cause: Supply voltage does not match the specification on the nameplate
Remedial action: Apply the correct voltage
Possible cause: The polarity of the supply voltage is wrong
Remedial action: Correct the polarity
Possible cause: The cables do not contact the terminals properly
Remedial action: Check the electrical contact between cables and correct if necessary
Possible cause: Load resistance too high
Remedial action: Increase the supply voltage to reach the minimum terminal voltage
No values visible on the display
Possible cause: Graphic display is set too bright or too dark
Remedial action: Increase or decrease the contrast with the Contrast display parameter
Navigation path: System → Display → Contrast display
Possible cause: The plug of the display cable is not connected correctly
Remedial action: Connect the plug correctly
Possible cause: Display is defective
Remedial action: Replace the display
No background lighting on the graphic display
Possible cause: There is insufficient power available
Remedial action: Increase the supply voltage
"Communication error" is indicated on the display when the device is started or the
display is connected
Possible cause: Electromagnetic interference influence
Remedial action: Check grounding of the device
Possible cause: Defective cable connection or display plug
Remedial action: Replace the display
HART communication not working
Possible cause: Communication resistor missing or incorrectly installed
Remedial action: Install the communication resistor (250 Ω) correctly
Possible cause: The HART modem is not properly connected
Remedial action: Connect the HART modem correctly
3) Available only for devices with SIL or WHG approval